GPU WORLD · GW-LC-CDU-65L
65 kW planning class liquid-to-liquid rack CDU
Multi-server sizing reviewSize a shared CDU for several GPU servers. Confirm each node’s liquid load, manifold branch duty and facility-water envelope before setting the rack design.
Fit and compatibility
- Provide each node’s design liquid load, minimum flow and allowable coolant supply temperature. Identify which nodes can be isolated during service.
- Confirm facility water flow, pressure and worst supply temperature, plus the rack or row footprint, equipment weight and electrical capacity.
Scope of supply
- Define the CDU, rack manifold interfaces and isolation points. Document whether redundant pumps, leak detection, a controls gateway and spares are required.
- Request vendor performance maps for the selected fluids and operating temperatures. Agree on power, monitoring and service clearances.
Operating conditions
- Add the coincident liquid loads for the installed nodes and document any future load allowance separately. Keep the residual air heat in the room cooling budget.
- Compare the combined load with the selected unit’s capacity at actual facility and equipment loop flows and approach temperature. Treat 65 kW as a planning class.
- Use the most demanding branch to establish available pump head. Evaluate manifold pressure and flow with nodes connected or isolated and at the specified filter condition.
Acceptance checks
- Bring nodes online in stages and record both loop flows, coolant temperatures, pump duty and branch flow under the agreed combined load.
- Exercise node isolation, controls alarms and any specified pump failover. Confirm that the remaining nodes stay inside their approved limits.
Technical references
Use these references to identify the platform and design requirements. GPU WORLD confirms the applicable assembly and operating conditions for each project.
CONFIGURATION & QUOTATIONSRequest a cooling quoteShare your server configuration and site conditions.Request a quote